IGS-NT Installation Guide
123
SG COM
SG OUT
VoutR
G
M
GAC
ESD 5330
AUX
Sync/Load ctrl:
Speed gov bias = 5,00 V
SpeedRegChar =
NEGATIVE
SG COM
SG OUT
VoutR
G
N
ESD 5111
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar =
NEGATIVE
SpeedGovLowLim = 4 V
SpeedGovHiLim = 6 V
SG COM
SG OUT
VoutR
2
25
GAC
EGS 104B
Sync/Load ctrl:
Speed gov bias = 5,00 V
SpeedRegChar =
NEGATIVE
SpeedGovLowLim = 4V
SpeedGovHiLim = 6V
SG COM
SG OUT
VoutR
L
A
GAC
SDG 735
Sync/Load ctrl:
Speed gov bias = 5,00 V
SpeedRegChar =
NEGATIVE
SpeedGovLowLim = 2,5V
SpeedGovHiLim = 7,5V
Tau act.= 1
WOODWARD
SG COM
SG OUT
VoutR
13
12
WOODWARD
ProAct II
3k3
Sync/Load ctrl:
Speed gov bias = 0,00 V
SpeedRegChar =
POSITIVE
SpeedGovLowLim = -2,5V
SpeedGovHiLim = 2,5V
SG COM
SG OUT
VoutR
12 -
11 +
WOODWARD
EPG
Hint:
For Woodward EPG speed governor (revision F) are limits:
SpeedGovLowLim = -3V
SpeedGovHiLim = +2V
Speed gov bias = -0,5 V
Sync/Load ctrl:
Speed gov bias =0 V
SpeedRegChar =
POSITIVE
SpeedGovLowLim = -3 V
SpeedGovHiLim = 3 V