IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
Setpoint: Derating2 end
This setpoint is used for adjusting the end point of the Power derating 2 function,
where the gen-set nominal power is reduced to the value adjusted by setpoint
Derated2 pwr.
See the chapter Power derating for details.
NOTE:
The setpoint actual physical dimension depends on configuration of the physical
analog input to which the logical input PowerDerating1 is assigned.
Setpoint: Derated2 pwr
This setpoint is used for adjusting the final power level for the Power derating 2
function. The nominal power is not reduced below this setpoint even if the
respective analog input increases further.
See the chapter Power derating for details.
Setpoint: TempByPwr Treq
The setpoint is used for adjusting the requested temperature for the Temperature-
By-Power control loop.
The Temperature-By-Power is active if the setpoint Load ctrl PtM is set to T BY
PWR position and the logical analog input LdCtrl:TByPwr is attached to the
physical analog input where the temperature is measured.
See also the setpoints TempByPwr int and TempByPwr gain.
NOTE:
As the "regulating action" of the Temperature-By-Power control loop is changing
of the gen-set power the regulated value (i.e. some temperature) must depend on
the gen-set power. Typical usage of this function is regulation of the output