IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
synchronized return to the mains. No continuous
parallel operation.
AMF gen-set without test-on-load function and with
synchronized return to the mains. No continuous
parallel operation.
Gen-set operating parallel to mains with additional
AMF functionality, synchronized return to the
mains.
Gen-set operating parallel to mains with additional
AMF functionality, switchover return to the mains
(e.g. if the mains breaker is not suitable for
synchronizing).
Gen-set operating only in parallel to the mains. No
island operation at all.
Setpoint: #Neutral cont
The setpoint is used for adjusting the behavior of the Neutral CB C/O output
according to actual site wiring.
The neutral contactor is used to connect the neutral wire (N) with the protective
wire (PE) in a TN-S system. This connection must exist in one moment at one
point of the circuit only.
The EACH option should be used if each gen-set has it's own neutral contactor.
Four-pole GCB must be used for this case.
ï‚· The output is always opened while the gen-set is not running.
ï‚· The output is always opened while the MCB is closed.
ï‚· While the gen-set is running and GCB is open, the output closes when