IGS-NT Combi, SW Version 3.0, ©ComAp May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
124
NOTE:
In the case that more IV displays are connected they all behave the same (they
are all clones of each other).
NOTE:
The binary inputs for external buttonst may be the following (depending on used
application): GCBButton, MCBButton, MGCBButton, FDRButton, BTBButton,
FaultResButton, HornResButton, StartButton, StopButton etc.
Setpoint: DispBaklightTO
Group
Basic settings
Range [units]
OFF, 1-240 min, NO TIMEOUT [min]
Related FW
3.0
Force value
possible
YES
Force value
possible
YES
Description
This setpoint adjusts timeout after which the display (internal display or IS display
#1) backlight is switched off.
NOTE:
When IntelliVision is used this setpoint does not adjust its behavior. Its backlight is
adjusted by internal IntelliVision "setpoint".
OFF
The backlight is off all the time
NO TIMEOUT
The backlight is on all the time
Setpoint: DispBklStrtOff
Group
Basic settings