engine reaching of it's operational temperature smoothly. The warming period is
finished either when the temperature reaches the warming level or if duration of
the warming period reaches Max warm time.
Setpoint: Warming temp
Group
Engine params
Range [units]
-32000 .. 32000 [°C]
Related FW
3.0
Force value
possible
YES
Description
This setpoint adjusts the warming temperature. The warming phase is finished
when either the water temperature at the logical analog input Warming temp
reaches this level or the Max warm time elapses.
NOTE:
See also the setpoint Warming load.
Setpoint: Max warm time
Group
Gener Protect
Range [units]
0 .. 3600 [s]
Related FW
3.0
Force value
possible
YES
Description
This setpoint adjusts the maximum duration of the warming phase after the genset
was sychchronized to the mains. The warming phase is finished when either the
water temperature at the logical analog input Warming Temp reaches this level or
the Max warm time elapses.
Setpoint: Cooling speed
Group
Engine Params
Range [units]
IDLE, NOMINAL
Related FW
3.0
Force value
possible
YES
Description
This setpoint is used to select whether the cooling phase is performed at idle or
nominal speed, i.e. whether the output Idle/Nominal is open or closed during the
idle phase.
NOMINAL
Gen-set performs cooling at nominal speed, generator voltage
and frequency protections remain active during cooling phase.
IDLE
Gen-set performs cooling at idle speed, generator protections
are not active in the cooling phase (except of Gen >V Sd).

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals