generator voltage and frequency are in limits.
Setpoint: Max Stab Time
Min Stab Time .. 3600 [s]
This setpoint adjusts the maximum time between the end of the idle period and reaching
proper generator voltage and frequency. If the proper generator voltage and frequency is
not reached within this period generator voltage and/or frequency alarm is issued and the
gen-set is stopped.
Setpoint: Warming load
This setpoint is used to adjust the requested load level during warming period in
% of the Nomin power.
The warming period takes place after the gen-set has been synchronized to the
mains if the temperature measured at the logical analog input Warming Temp is
below the value of Warming temp. The gen-set load is maintained at Warming
load, which should be adjusted to cca 20-30% of the nominal load to allow the