IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
This setpoint is used to adjust the delay of stopping the next gen-set when the
actual load reserve rises above the adjusted load reserve for stop.
Setpoint: #SlowStopDel
This setpoint is used to adjust how long the particular gen-set will suppress it's
own Slow stop alarm to give chance to another gen-set to start and replace the
defective one.
If there isn't any available gen-set to start, the alarm is not suppressed.
Setpoint: #MinRunPower 1
This setpoint is used to adjust certain minimum value of the sum of nominal power
of all running gen-sets. If the function is active, then the gen-sets would not be
stopped, although the reserve for stop is fulfiled, if the total remaining nominal
power dropped below this minimal value.
There are 3 different MinRunPower setpoints, this particular one is activated by
the input MinRun power 1.
NOTE:
If more than one binary input for MinRunPower activation is closed MinRunPower
with higher number is used (i.e. binary inputs with higher number have higher
priority).
When no binary input is closed, then minimal running power is 0.
Setpoint: #MinRunPower 2
This setpoint is used to adjust certain minimum value of the sum of nominal power
of all running gen-sets. If the function is active, then the gen-sets would not be
stopped, although the reserve for stop is fulfiled, if the total remaining nominal
power dropped below this minimal value.
There are 3 different MinRunPower setpoints, this particular one is activated by
the input MinRun power 2.
NOTE:
If more than one binary input for MinRunPower activation is closed MinRunPower
with higher number is used (i.e. binary inputs with higher number have higher
priority).