EasyManuals Logo

ComAp IS-NTC-BB Reference Guide

ComAp IS-NTC-BB
361 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #235 background imageLoading...
Page #235 background image
IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
235
Value: Object PF
Group
Mains values
Units
-
Related FW
3.0
Description
Cos-phi factor at the load. This value is computed indirectly from the values
Object P and Object Q.
Value: Object LChr
Group
Mains values
Units
-
Related FW
3.0
Description
Character of the object load. This value is computed indirectly from the values
Object P and Object Q.
Value: MaxVectorS
Group
Mains values
Units
º
Related FW
3.0
Description
This is maximal measured value of vector shift of the generator voltage. The value
is reset to 0 automatically in the moment of closing the GCB.
Value: Mains Avg V1
Group
Mains values
Units
V
Related FW
3.0
Description
This value shows average Mains voltage in phase L1.
Value: Bus Avg V1
Group
Bus values
Units
V
Related FW
3.0
Description
This value shows average Bus voltage in phase L1.
Value: Mains Avg V2
Group
Mains values
Units
V
Related FW
3.0
Description
This value shows average Mains voltage in phase L2.
Value: Bus Avg V2
Group
Bus values

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals