IGS-NT Combi, SW Version 3.0, ©ComAp May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
242
Units
X
Related FW
3.0
Description
This data object is intended for remote control of the gen-set via the
communication if some kind of data is to be passed into the controller.
This object can be written via the communication (e.g. Modbus) without any
limitation. Use GenConfig function Generate Cfg Image to get the communication
object number or register number of this particular value object. See an example
at the object ExtValue1.
Group: Load shedding
Value: StatLdShed
Group
Load shedding
Units
-
Related FW
3.0
Description
The value indicates the current load shedding stage. 0 indicates that the load
shedding is not active. See the chapter Load shedding for more details.
Group: Analog CU
Value: UBat
Group
Analog CU
Units
V
Related FW
3.0
Description
Voltage at the controller power supply terminals.
Value: CPU Temp
Group
Analog CU
Units
ºC
Related FW
3.0
Description
Temperature inside the controller (on the CPU).
Value: D+
Group
Analog CU
Units
V
Related FW
3.0
Description
Voltage measured at the D+ terminal. If this voltage is > 80% of the Ubat the D+
terminal is evaluated as active and the engine is evaluated as running. See also
the chapter Start sequence.

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals