This is a software function only. It can be extended by a "hard-wired" emergency
stop function, which means disconnecting power supply from the controller
outputs.
Binary input: Test on load
This input is used to force the genset to take over the load in TEST mode.
NOTE:
This logical input can be configured together with the input Remote TEST onto
one controller terminal and then the "test with load" function can be activated by
one signal. That means e.g. if a mains supply interruption is expected, the
controller can be forced to start, take the load over and disconnect the mains prior
to the interruption occurs. Then, after the mains has been restored, the signal is
removed and the controller transfers the load back to the mains.
Binary input: SPI enable
This binary input, together with the input MultipleEnable are used to select the
application mode.
APPLICATION MODE SELECTION TABLE
NOTE:
A change of the application mode is accepted when the controller is powered-
on or while it is in emergency manual mode. If you need to change the
application mode without switching the controller off switch the controller to
Emerg. manual, then change the application and finally switch the emergency
manual off.
Binary input: MultipleEnable
This binary input, together with the input SPI Enable are used to select the
application mode.
APPLICATION MODE SELECTION TABLE