used as stop command for ECU-controlled engines, which support stop command
via the communication bus (e.g. J1939).
Binary output: Syst res OK
The output is closed while the actual reserve is above the selected reserve for
start.
Binary output: Syst res 1 OK
The output is closed while the actual reserve is above the reserve for start from
the reserve set #1.
Binary output: Syst res 2 OK
The output is closed while the actual reserve is above the reserve for start from
the reserve set #2.
Binary output: Syst res 3 OK
The output is closed while the actual reserve is above the reserve for start from
the reserve set #3.
Binary output: Syst res 4 OK
The output is closed while the actual reserve is above the reserve for start from
the reserve set #4.
Binary output: AllAvailGS run
The output is closed while all gen-sets in the group, which participate in the power
management, are running and loaded.
Binary output: Speed up
This output together with the complementary output Speed dn are designed for
speed and power control at gen-sets where the speed governor does not support
analogue control.
NOTE:
The governor is recommended to be configured for droop function when these
outputs are used for power control.