IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
NOTE:
The alarm Wrn SpdRegLim is disabled when this output is used (configured onto
any controller terminal or virtual output).
Binary output: Speed dn
This output together with the complementary output Speed up are designed for
speed and power control at gen-sets where the speed governor does not support
analogue control.
NOTE:
The governor is recommended to be configured for droop function when these
outputs are used for power control.
NOTE:
The alarm Wrn SpdRegLim is disabled when this output is used (configured onto
any controller terminal or virtual output).
Binary output: AVR up
This output together with the complementary output AVR dn are designed for
voltage and power factor control at gen-sets where the AVR does not support
analogue control.
NOTE:
The AVR is recommended to be configured for droop function when these outputs
are used for power factor control.
NOTE:
The alarm Wrn VoltRegLim is disabled when this output is used (configured onto
any controller terminal or virtual output).
Binary output: AVR dn
This output together with the complementary output AVR up are designed for
voltage and power factor control at gen-sets where the AVR does not support
analogue control.
NOTE:
The AVR is recommended to be configured for droop function when these outputs
are used for power factor control.
NOTE:
The alarm Wrn VoltRegLim is disabled when this output is used (configured onto
any controller terminal or virtual output).
Binary output: SPI mode