IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
the input HornResButton is activated.
Binary output: StartButnEcho
This output provides 1s pulse when:
Start button is pressed on the controller front panel or
Start button is pressed on any of external local/remote terminals or
start command is received via communication line or
the input StartButton is activated.
Binary output: StopButnEcho
This output provides 1s pulse when:
Stop button is pressed on the controller front panel or
Stop button is pressed on any of external local/remote terminals or
stop command is received via communication line or
the input StopButton is activated.
Binary output: MCBButnEcho
This output provides 1s pulse when:
MCB button is pressed on the controller front panel or
MCB button is pressed on any of external local/remote terminals or
MCB close/open command is received via communication line or
the input MCBButton is activated.
Binary output: GCBButnEcho
This output provides 1s pulse when:
GCB button is pressed on the controller front panel or
GCB button is pressed on any of external local/remote terminals or
GCB close/open command is received via communication line or
the input GCBButton is activated.