6.3 Current Output in the Service Mode
The analog output can be set to 2 or 4 mA in the service mode. Here is a listing of all possible modes:
Error
(critical error)
Service
(non critical error)
Display at the Statox 503
Control Module
2-wire operation
2 mA
2 mA
4 mA
Service Mode
„0“
3-wire operation
0 mA
2 mA
4 mA
Error 2
Service Mode
„0“
Caution: In the menu REPLACE the sensor head will always remain in the service mode, even if there is
no sensor plugged in.
If you operate the sensor head as a SIL - device EN 61508 (functional safety), the analog output must
be programmed to 2 mA in the service mode!
As soon as programmed, the output is active.