8
+ - 0
10-15 mm
6 mm
50 mm
Strip the cable end as shown here.
Push the cable shield backwards and shorten it to
10-15 mm.
Push the metal spring onto the cable until it makes
good contact with the shield.
Push the cable into the cable gland to the end stop
of the metal spring.
Fasten the nut slightly.
The cable isolation end shall match with the inner
end of the cable gland. (Arrow)
Now fasten the nut.
The package includes a ferrite core which will help
to avoid electromagnetic interferences. Push it over
the connection cable before connecting it.
Connect the wires to the terminal plug. This plug
can be removed, in order to ease installation.
Terminal 3 must only be connected for 3 - wire
operation. Then replug the terminal plug.
Connect the ground terminal to the ground of the
building. In order to avoid ground loops only ground
this end of the cable! If installed in a classified area,
an equal potential all along the intrinsically safe
circuit is required.
As soon as power is on, the sensor head performs
a selftest and then displays its operating program
index.
See chapter 5: Start up.