4 - 3 0 l Op e ra ti o n
C o n t r o l Fun c ti o n D es c ri p ti o ns - R W
C o n f i g u r a ti o n (c on t in u ed )
Dewpoint Setup screen
To access the Dryer Dewpoint Sensor Setup screen:
1 Press the Settings button from the Home screen.
2 Press the I/O Setup button.
3 Press the Dewpoint Setup button.
The Dryer Dewpoint Sensor Setup screen provides the user with the ability to adjust the set-
tings for the Dewpoint sensors. This screen allows for adjustment of:
• Sensor minimum and maximum
• Delivery air dewpoint sample rate, sample averages, and offset
• Return air dewpoint sample rate, sample averages, and offset
To change a setpoint:
1 Press the text inside
white box with thick
black outline of the set-
ting you would like to
change.
2 Use the keypad to enter
the new setting. Setting
range will be displayed
at the bottom of the pop
up keypad.
3 Press the enter key.
NOTE: Proper login is required to
change these settings.
✐
(continued)
NOTE: These are factory settings and
should not need changed. Consult
with Conair before making any
changes to these settings. Conair’s
Instant Access 24/7 Parts and Service
number is 800-458-1960. Outside
the U.S., dial 814-437-6861.
✐