Operating Manual PG11 / PGE11 Page 27
5.2 Perform a check of the Gas Detector accuracy
The PG11 and PGE11 have been calibrated for life at the Factory and do not require to be recalibrated. At
the Factory great care has been taken to take into account environmental effects such as gas concentration,
the temperature of the gas, ambient pressure and humidity to make a very precise calibration of the
Detectors. Calibrating in field it is very difficult to take such considerations so it is therefore not possible to
calibrate the Detector in field since it would not improve the accuracy. Below is the procedure to verify the
Detector accuracy.
Requirements:
Gas Sample kit
Gas cylinder with calibrated test gas
o Concentration of test gas recommended to 50 ±10 %FS
o Flow rate shall be between 0.5 and 1.1 liters/min.
Flexible gas tube between Gas cylinder and Gas Sample kit
Data logger connected to the 4.20 mA.
Procedure to verify accuracy of the Detector:
1. Power up and allow the Gas Detector to warm for at least 20 minutes.
2. Insert Gas Sample kit as shown in illustration below.
3. Connect the tube from the Gas cylinder to one of the nozzles on the Gas Sample kit.
4. Slide the Gas Sample kit on the outside of the detector sensor section as shown below.
5. Apply the gas from the Gas cylinder with a gas flow between 0.5 - 1.1 liters/min.
6. Allow for gas reading to stabilize for at least one minute.
7. Start the data logger and perform logging for two minutes.
8. Calculate average gas value and standard deviation from the data logger and compare with the
specifications of the detector for Accuracy.