Operating Manual PG11 / PGE11 Page 6
1.1 Technical Specifications
Gas Detection by Dual band Optical absorption in target gases.
Solid-state Infrared SafeSource™. Temperature compensated Optical Gas detection for rugged applications
Gases and
maximum
measuring
range
Detector configured from factory for one of the following gases with 100 %vol as maximum range:
● Methane
● Propane
● Ethylene
● Butane
● CO2
● Biogas (mixture of CH4 in CO2)
Temperature
Humidity
Vibration
Severe vibration conditions
Storage: -60 to +85°C / -76 to +185°F
Operating: -40 to +75°C / -40 to +167°F (Desert)
-40 to +65°C / -40 to +149°F (Standard)
-55 to +65°C / -76 to +149°F (Arctic)
0 - 99 %RH
Resistant to shock and vibration.
Tested for mounting on applications such as diesel engines and compressors
(vibrations up to 4G).
M20 (standard), M25, 1/2" NPT or 3/4" NPT
2.5 mm² (Stranded), 4 mm² (Solid)
24 V DC, range 18 - 50 VDC
< 3 W average (standard configuration)
< 5 W average (arctic configuration)
Soft boot-up to keep rush current less than 1 A
Performance
key
characteristics
T90 ≤ 2 sec, with Environment Shield
T20 ≤ 0.5 sec, with Environment Shield
Ambient above -20°C
Ambient below -20°C
< 2 minutes,
< 20 minutes
Calibrated at the factory, no field calibration shall be done.
Current source or sink 4 - 20 mA
HART® digital communication
Modbus RTU for OptoCom™ modules, Safety protocols or Condition monitoring.
Multicolour indicator light in front of detector.
The electronics have been designed to withstand powering up the detector with terminal wires accidentally
being swapped.
Continuous self-verification of all important functions.
3.4 kg (3.9 kg with the optional steel rear lid)