5604 Input/Output (I/O) Module - Hardware Manual
October 19, 2007
Digital input 32 returns the DC/DC converter status.
0 = DC/DC converter off
1 = DC/DC converter on
Digital input 33 returns the DC/DC converter over current status.
0 = Over current not detected
1 = Over current detected
Digital input 34 returns the digital output mismatch status.
0 = No mismatch
1 = One or more digital outputs mismatch
Digital Output 32 is used to control the DC/DC converter.
0 = DC/DC converter off
1 = DC/DC converter on
The 12V to 24V DC/DC converter is turned on when the
LED power is enabled. This feature is provided for service
and diagnostics.
Digital Output 33 is used to control the VLoop power supply.
0 = VLoop output off
1 = VLoop output on
The VLOOP output is turned on when the LED power is
enabled. This feature is provided for service and
diagnostics.
Digital Outputs 34 and 35 control the SCADAPack 5604 I/O Module Analog Input
filters.
Filter Setting Digital Output 35 Digital Output 34
< 3 Hz OFF OFF
6 Hz OFF ON
11 Hz ON OFF
30 Hz ON ON