• The default serial communication parameters are used. See section 9.1-RS-232 Serial
Communication Ports for default parameters.
• The default TCP/IP parameters are used for the Ethernet port. See the 10.1.1-TCP/IP Settings
subsection above for default parameters.
• The default Modbus/TCP parameters are used for the Ethernet port. See section 10.1.2-
Modbus/TCP Settings for default parameters.
• The TelePACE or ISaGRAF application program is erased.
• The TelePACE or ISaGRAF C/C++ application program is erased.
• The controller is unlocked.
COLD BOOT mode is selected by performing a COLD BOOT using the following procedure:
1. Remove power from the controller.
2. Hold down the LED POWER button.
3. Apply power to the controller.
4. Continue holding the LED POWER button for 25 seconds until the STAT LED begins to flash
on and off continuously.
5. Release the LED POWER button.
Note: If the LED POWER button is released before the STAT LED begins to flash, the
SCADAPack 32 controller will start in SERVICE mode.
11.2 LED Indicators
There are 23 LEDs on the SCADAPack 32 controller board. These LEDs are used to indicate the
operational status of the controller. All LEDs except the 5V LED can be disabled to conserve power.
Refer to section 11.3-Led Power Control subsection below for details.
The following table describes functions of the LEDs on the SCADAPack 32 controller board.
LED Function
5V On when 5V power is present in the SCADAPack 32
controller. The controller must have 5V power to operate.
5V power is supplied by the SCADAPack 32 internal power
supply or from an external model 5103 power supply.
RUN On when a TelePACE or ISaGRAF application program is
running in the SCADAPack 32 controller. This LED may be
controlled by a C++ Tools application, in which case the
application will control the LED status.
LEDS On when LED power is enabled.
STAT This LED is normally off. The LED will blink when an error
exists. Refer to section 11.4-Status LED and Output for
more information on this LED and the STATUS output.
FORCE On when and SCADAPack 32 I/O points are forced in a
TelePACE application, or locked in an ISaGRAF
application.
INT/Counters 0
INT/Counters 1
INT/Counters 2
On when a signal is applied to the corresponding input.
INT On when a signal is applied to the INT input
SCADAPack 32 Controller Hardware Manual
May 24, 2006
40