DC power
Output
16Vrms applied
20-24V with 1.0Vp-p maximum ripple.
300mA available at 5V/0.5A, de-rate linearly to 100mA
available at 5V/1.3A
Efficiency
80%, 12V on DC PWR input
14.5 I/O Capacity
5000 Series I/O
Expansion
Capacity
Maximum 40 I/O modules with a further limitation of 16
modules of any one type.
512 digital outputs using 32 point digital output modules
512 digital inputs using 32 point digital input modules
128 analog inputs using 8 point analog input modules
64 analog outputs using 4 point analog output modules
32 counter inputs using 4 point counter input modules
Example: 16 of the 32 point digital output modules + 16 of
the 32 point digital input modules + 8 of the 8 point analog
input modules would yield an expansion of 1088 I/O points.
14.6 Digital Inputs
Input Points
3 Digital Input/Counter, 1 Interrupt
opto coupler isolation
Digital Input,
Counter
24Vrms/30V maximum input
10Vrms/10V minimum ON input
2V maximum OFF input
Typical threshold voltage is 4 to 6V
Typical input hysteresis 1.0V
Typical input current 2.5mA at 10V
7mA at 24V
Counter Input
Frequency
(Counter 0, 1, 2)
5kHz maximum with filter OFF
30Hz maximum with filter ON
Counter Input
Frequency
(Counter 3)
500Hz maximum
14.7 Digital Outputs
Status Output
(STATUS)
Opto coupler open collector transistor
30V, 60mA
opens on fault
SCADAPack 32 Controller Hardware Manual
May 24, 2006
53