Baud Rate
(COM3)
1200, 2400, 4800, 9600, 19200, 38400, 57600 and
115200.
Default: 9600
Parity
none, even, or odd
Default: none
Word Length
7 or 8 bits
Default: 8 bits
Stop Bits
1 or 2 bits
Default: 1 bit
Duplex (COM1,
COM2, COM4)
full or half with RTS/CTS control
Default: full
Duplex (COM3)
half with RTS/CTS control
Cable Length
RS-232 –maximum 50 ft (15.2 m)
RS-485 –maximum 4000 ft (1200 m)
Protocol
TeleBUS (compatible with Modbus RTU and Modbus
ASCII)
DF1 and DNP Protocols optional
default: Modbus RTU
Ethernet
RJ-45 modular connector
10BaseT (twisted pair)
10M bits per second.
Protocol Modes
slave, master, master/slave, store and forward
14.3 Visual Indicators
COM1,COM2,
COM4
received data (RxD) LED
transmitted data (TxD) LED
clear to send (CTS) LED
data carrier detect (DCD) LED
Ethernet LAN
Ethernet network receive or transmit data LAN LED
Ethernet port connected to a network LINK LED
I/O module LED power status LED
Status LED (shows functional status)
5V power LED (LED power not applicable)
Run LED
Forced I/O LED
Counter Inputs 0, 1, 2 and 3 LEDs
Digital Inputs
INT/CTR, CTR0, CTR1, CTR1
Push-button
LED power toggle
14.4 Power Supply
Power Input
AC/DC PWR IN
16Vrms ±20%
14 to 30Vdc
DC power Input
DC PWR
30V maximum
10.7V typical turn on
9V typical turn off
5 Volt Power
Output
5V at 1.3A capacity
5V at 500 mA required by SCADAPack 32 controller
SCADAPack 32 Controller Hardware Manual