EasyManua.ls Logo

Control Microsystems SCADAPack 32 - Analog Input Range Selection; Analog Output Range Selection; Figure 20: Analog Input Offset DIP Switches

Default Icon
55 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11.5.1 Analog Input Range Selection
The analog input channels on the integrated I/O modules on some versions of the SCADAPack 32
controller can be configured for a 0% or 20% offset using switch ‘Options 1’ on SW1. With the 0%
offset, the input signal measurement range is 0-20mA in current mode or 0-5V in voltage mode.
With the 20% offset, the input signal measurement range is 4-20mA in current mode or 1-5V in
voltage mode.
On the SCADAPack P4 equipped with the 5601 I/O board, select the 0% offset by sliding switch
‘Options 1’ on SW1 to the left as shown in the figure below. Select the 20% offset by sliding the
switch to the right.
Slide the actuator
to this side for
4-20mA or 1-5V
Slide the actuator
to this side for
0-20mA or 0-5V
How to Set the Range Switch:
Determine the desired range.
Slide the actuator to the side of
the switch shown in gray.
0-20mA or 0-5V
In
p
uts
SW 1
2
1
2
3
4
0
1
not used
Options
Filters
SW 1
2
1
2
3
4
0
1
not used
Options
Filters
4-20mA or 1-5V
In
p
uts
Figure 20: Analog Input Offset DIP Switches.
This option is not available on the SCADAPack P4A controller with the 5604 I/O module. On the
SCADAPack P4B controller with the 5606 I/O module, the settings are selected in software. See the
5606 Input-Output Module hardware manuals for details.
Note: The default setting for the analog inputs on the SCADAPack P4 and P4B is 0% offset or a
measurement ranges of 0-20mA in current mode or 0-5V in voltage mode.
11.5.2 Analog Output Range Selection
The optional analog output channels of the integrated I/O modules on the SCADAPack 32 controller
can be configured for a 0% or 20% offset using switch ‘Options 2’ on SW1. With the 0% offset, the
output signal ranges from 0-20mA in current mode or 0-5V in voltage mode. With the 20% offset,
the output signal ranges from 4-20mA in current mode or 1-5V in voltage mode.
On the SCADAPack P4 and P4A controllers respectively equipped with the 5601 and 5604 I/O
modules, select the 0% offset by sliding switch ‘Options 2’ on SW1 to the left as shown in the figure
below. Select the 20% offset by sliding the switch to the right. On the SCADAPack P4B the settings
are selected in software. See the 5606 Input-Output Module hardware manual for details.
SCADAPack 32 Controller Hardware Manual
May 24, 2006
44

Table of Contents

Related product manuals