CT2001 Touchscreen Programmable Thermostat
52
Table 3. Installer Setup Menu. (CONTINUED)
Installer Setup
Name
Settings
Notes
Initial
Setting
Record
Cycles per hour
(cph) for Emer
3-3 cph for hot water systems and high
efficiency (90% or better) furnaces.
5-5 cph for standard fossil fuel forced air (less
than 90% efficient or better) systems.
9-9 cph for electric strip heat for heat pumps.
Only shown if 2H/1C or
3H/2C heat pump is selected.
Continuous
Backlight
0-Backlight function disable.
1-Backlight function enable.
If set to 1 , the backlight will
illuminate for 10 seconds
after any touchscreen press.
Changeover
0-manual changeover (factory setting).
1-auto changeover.
Dead band
Heating and cooling set-points can be set no
closer than chosen value:
2-2°F (1.5°C)
3-3°F (2°C)
4-4°F (2.5°C)
5-5°F (3°C)
6-6°F (3.5°C)
7-7°F (4°C)
8-8°F (4.5°C)
9-9°F (5°C)
Shown only if automatic
changeover is selected.
Temperature
Indication
Scale
0-fahrenheit temperature display (factory
setting).
1-celsius temperature display.
When it is changed, the
schedule must be
reprogrammed.