Coolerado M50C - Appendix 10 - M50 B Air Flow Performance Table

Default Icon
63 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Coolerado Installation
Page 43 of 63
Appendix 10: M50C, Air Flow Performance Table;
200 to 277 VAC, 1 phase motor
Coolerado M50A Performance Table*
External Static
Pressure
Full Speed Product Air
Flow
Approx.
Product
Air Wet
Bulb
Approach
Product Approx.
= WB + below
Working Air Flow
Inches
H2O
Pascal CFM CMH LPS F C CFM CMH LPS
0.00
0
1350
2290
635
94%
2
1.1
1000
1700
470
0.10
24.9
1280
2170
601
95%
2
1.1
950
1610
445
0.20
49.8
1200
2050
567
95%
1
.6
890
1510
420
0.30
74.7
1140
1930
534
98%
1
.5
840
1430
395
0.40
99.5
1060
1810
500
100%
0
0
790
1340
370
0.50
124.4
990
1690
466
103%
-1
-.6
730
1240
345
0.60
149.3
920
1560
433
107%
-2
-1.1
680
1150
320
0.70
174.2
850
1440
399
110%
-3
-1.7
630
1070
295
0.80
199.1
780
1320
366
113%
-4
-2.2
570
970
271
0.90
224
710
1200
332
117%
-5
-2.8
520
880
246
1.00
248.9
630
1080
298
120%
-6
-3.3
470
800
221
* Performance at sea level: Performance increases ~0.5% for every 1,000 feet / 305 m increase above sea level.
Example: Design 98F DB / 62F WB, 0.1” ext. static, 98 - 62 = 36, 36 * 0.95 = 34.2, 98 34.2 = 63.8 ºF Product Air Temperature ≈
Design WB + 2 = 64 ºF
Example: Design 36C DB / 16C WB, 0.1” ext. static, 36 - 16 = 20, 20 * 0.95 = 19, 36 19 = 17C Product Air Temperature ≈ Design
WB + 1.1C = 18.1 ºC
380 480 VAC, 3 Phase motor
Coolerado M50A Performance Table*
External Static
Pressure
Full Speed Product Air
Flow
Approx.
Product
Air Wet
Bulb
Approach
Product Approx.
= WB + below
Working Air Flow
Inches
H2O
Pascal CFM CMH LPS F C CFM CMH LPS
0.6
149
1350
2290
635
94%
2
1.1
1000
1700
470
0.7
174
1260
2140
594
95%
2
1.1
930
1580
440
0.8
199
1220
2072
575
95%
1
.6
900
1529
425
0.9
224
1160
1970
547
98%
1
.5
860
1460
405
1
249
1100
1869
519
100%
0
0
814
1383
384
1.1
273
1040
1767
490
103%
-1
-.6
770
1308
363
1.2
298
980
1664
462
107%
-2
-1.1
725
1231
342
If the External static supply pressure is less than o.6” wc (149 Pa) the control board potentiometer must be turned down
to a maximum pressure drop across the supply side of the HMX, (after filter to supply plenum), of 1.1” wc (224 Pa).