Coolerado Installation
Page 48 of 63
Appendix 13: C60A Air Flow Performance Table
Coolerado C60 Performance Table*
External Static
Pressure
Full Speed Product Air
Flow
Approx.
Product
Air Wet
Bulb
Approach
Product Approx.
= WB + below
Working Air Flow
Inches
H2O
Pascal CFM CMH LPS F C CFM CMH LPS
0.00 0 1550 2630 729 94% 2 1.1 1200 1380 560
0.10 24.9 1470 2490 690 95% 2 1.1 1140 1310 540
0.20 49.8 1380 2340 650 96% 1 .6 1070 1230 500
0.30 74.7 1300 2200 611 98% 1 .5 1000 1150 470
0.40 99.5 1220 2070 570 100% 0 0 940 1080 440
0.50 124.4 1130 1910 530 103% -1 -.6 870 1000 410
0.60 149.3 1050 1780 490 107% -2 -1.1 810 930 380
0.70 174.2 970 1640 460 110% -3 -1.7 750 860 350
0.80 199.1 900 1520 420 113% -4 -2.2 700 800 330
0.90 224 810 1370 380 117% -5 -2.8 630 720 300
1.00 248.9 720 1220 340 120% -6 -3.3 560 640 260
* Performance at sea level: Performance increases ~0.5% for every 1,000 feet / 305 m increase above sea level.
Example: Design 98F DB / 62F WB, 0.1” ext. static, 98 - 62 = 36, 36 * 0.95 = 34.2, 98 34.2 = 63.8 ºF Product Air Temperature
Design WB + 2 = 64 ºF
Example: Design 36C DB / 16C WB, 0.1” ext. static, 36 - 16 = 20, 20 * 0.95 = 19, 36 19 = 17C Product Air Temperature ≈ Design
WB + 1.1C = 18.1 ºC