COOLIUS A50
6.6 Report
The machine records the refrigerant usage monthly for the previous twelve months. Beyond this period, it will
overwrite the data for the month in question.
1. Turn COOLIUS SELECT to select the following coun-
ters:
“REFRIGERANT RECOVERED FROM
A/C SYSTEM”
“REFRIGERANT RECOVERED FROM
EXTERNAL TANK”
“REFRIGERANT FILLED TO A/C SYSTEM”
The display shows in sequence all the months and the total per year.
2. Press START to print the report.
6.7 Scale reset
At the purpose to compensate the scale deviation, perform the following instructions:
1. Turn COOLIUS SELECT to select
OTHER SELECTIONS, conrm by ENTER,
2. Turn COOLIUS SELECT to select
SCALE RESET
3. Press ENTER to conrm.
4. Turn COOLIUS SELECT to select the scale:
“REFRIGERANT WEIGHT SCALE”
“WASTE OIL WEIGHT SCALE”
5. Press ENTER to conrm.
6.7.1 Refrigerant Weight scale
1. Lift the knob on the back side of the machine, move it to
the left and turn it in clockwise direction in order to lock it
into “safety position”.
2. Press START key to conrm scale unloaded.
WARNING! Conrm by START only if the scale is unloaded!
01/2018
R134a recovered
Kg. 10.0
2018
Total
R134a recovered
Kg. 210
Scale reset

Select:
Refrig. Weight scale
Unload weight scale
(safety position)