7
2.3 Product Protection Functions
Reverse polarity protection of DC input
AC and DC Short circuit protection
Anti-islanding protection with bi-directional frequency perturbation
DC Input and AC output over-voltage protection
DC Input over-current protection
DC input insulation against ground monitoring
DC injection of AC output
AC output voltage and frequency monitoring
Leakage current against ground monitoring
External environmental temperature monitoring
IGBT power module temperature monitoring
2.4 Smart Inverter Functions and default Activation
Function
IEEE1547-2014
Rule 21
ISO-NE
Anti-islanding
Enabled
Enabled
Enabled
Low/High Voltage Ride-Though
N/A
Enabled
Disabled
Low/High Frequency Ride-
Though
N/A
Enabled
Enabled
Dynamic Volt/VAR Operation
N/A
Enabled
Disabled
Ramp Rate
N/A
Enabled
Enabled
Fixed Power Factor
N/A
Disabled
Disabled
Reconnect by “Soft-Start”
N/A
Enabled
Enabled
Frequency-Watt
N/A
Enabled
Disabled
Volt/Watt
N/A
Enabled
Disabled