EasyManua.ls Logo

CPS SCH100KTL-DO-600 - Page 80

CPS SCH100KTL-DO-600
111 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
76
Table 5-4 LVRT and HVRT Parameters
LVRT (Enable Table 5.7 - 9)
Parameter name
Description
Range
Grid code
IEEE-1547
Grid code
RULE-21
Grid code
ISO-NE
LVRTVoltPara
(1,2)
Threshold LVRT
(1
st
or 2
nd
point)
{0%, 100 -%}
{0%, 100%}
{0%}
{0%}
{0%}
{0%}
{0%}
{0%}
LVRTTimePara
(1,2)
Time of LVRT
(1
st
or 2
nd
point)
{0, 655}
{0, 655}
{0}
{1.2}
{0}
{1.5.72}
{0}
{0.16}
LVRTVoltPara
(3,4)
Threshold LVRT
(3
rd
or 4
th
point)
{0%, 100%}
{0%, 100%}
{45%}
{45%}
{50%}
{50%}
{30%}
{45%}
LVRTTimePara
(3,4)
Time of LVRT
(3
rd
or 4
th
point)
{0, 655}
{0, 655}
{1.2}
{10.5}
{1.2}
{10.5}
{0.16}
{0.21}
LVRTVoltPara
(5,6)
Threshold LVRT
(5
th
or 6
th
point)
{0%, 100%}
{0%, 100%}
{65%}
{65%}
{70%}
{70%}
{45%}
{65%}
LVRTTimePara
(5,6)
Time of LVRT
(5
th
or 6
th
point)
{0, 655}
{0, 655}
{10.5}
{20.5}
{10.5}
{20.5}
{0.37}
{0.37}
LVRTVoltPara
(7,8)
Threshold of LVRT
(7
th
or 8
th
point)
{0%, 100%}
{0%, 100%}
{83%}
{83%}
{88%}
{88%}
{65%}
{88%}
LVRTTimePara
(7,8)
Time of LVRT
(7
th
or 8
th
point)
{0, 655}
{0, 655}
{20.5}
{20.5}
{20.5}
{20.5}
{3.05}
{3.25}
HVRT (Enable Table 5.7 -10)
Parameter name
Description
Range
Grid code
IEEE-1547
Grid code
RULE-21
Grid
code
ISO-NE
HVRTVoltPara
(1,2)
Threshold of HVRT
(1
st
or 2
nd
point)
{100%, 135%}
{100%, 135%}
{125%}
{125%}
{125%}
{125%}
{120%}
{120%}
HVRTTimePara
(1,2)
Time of Level
HVRT
(1
st
or 2
nd
point)
{0, 655}
{0, 655}
{0}
{0.8}
{0}
{0.11}
{0}
{0.16}
HVRTVoltPara
(3,4)
Threshold of HVRT
(3
rd
or 4
th
point)
{100%, 135%}
{100%, 135%}
{124%}
{124%}
{120%}
{120%}
{120%}
{117.5%}
HVRTTimePara
(3,4)
Time of Level
HVRT (3
rd
or 4
th
point)
{0, 655}
{0, 655}
{0.8}
{12.5}
{0.11}
{12.5}
{0.25}
{0.25}
HVRTVoltPara
(5,6)
Threshold of HVRT
(5
th
or 6
th
point)
{100%, 135%}
{100%, 135%}
{115%}
{115%}
{110%}
{110%}
{117.5%}
{115%}
HVRTTimePara
(5,6)
Time of Level
HVRT (5
th
or 6
th
point)
{0, 655}
{0, 655}
{12.5}
{12.5}
{12.5}
{12.5}
{0.55}
{0.55}
HVRTVoltPara
(7,8)
Threshold of HVRT
(7
th
or 8
th
point)
{100%, 135%}
{100%, 135%}
{115%}
{115%}
{110%}
{110%}
{115%}
{110%}
HVRTTimePara
(7,8)
Time of Level
HVRT (7
th
or 8
th
point)
{0, 655}
{0, 655}
{12.5}
{12.5}
{12.5}
{12.5}
{10.5}
{10.5}

Related product manuals