EasyManua.ls Logo

Crestron Horizon HZ-THSTAT - Page 152

Crestron Horizon HZ-THSTAT
179 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product Manual Doc. 8622E HZ-THSTAT 152
l
TS1 Usage: Defines how remote sensor channel 1 is used by the thermostat.
o
Omit: (Default) Omits channel from thermostat operation
o
Space: Adds channel to space temperature/humidity average
o
Outdoor: Adds channel to outdoor temperature/humidity average
o
Floor: Adds channel to slab (floor) temperature average
o
Changeover: Used to determine if the thermostat should be operating in Heat or Cool
mode. The changeover sensor should be placed on the feed pipe. Only one sensor (TS1 or
TS2) can be designated as the changeover sensor. The changeover option is only available
for the FCU 2-Pipe Heat/Cool system type.
l
TS2 Usage: Defines how remote sensor channel 2 is used by the thermostat.
o
Omit: (Default) Omits channel from thermostat operation
o
Space: Adds channel to space temperature/humidity average
o
Outdoor: Adds channel to outdoor temperature/humidity average
o
Floor: Adds channel to slab (floor) temperature average
o
Changeover: Used to determine if the thermostat should be operating in Heat or Cool
mode. The changeover sensor should be placed on the feed pipe. Only one sensor (TS1 or
TS2) can be designated as the changeover sensor. The changeover option is only available
for the FCU 2-Pipe Heat/Cool system type.
l
Wall Type: Defines the wall type that the thermostat is installed into for accurate temperature
readings. Select Non-Insulated (hollow) or Insulated.
l
Local Sensor Temperature Trim: Adjusts local sensor temperature measurement. Select -6 to
+6for Fahrenheit (-3.0 to +3.0 for Celsius). The default setting is 0.
l
TS1 Temperature Trim: Adjusts temperature sensed by temperature sensor(s) attached to TS1
input. Select -6 to +6for Fahrenheit (-3.0 to +3.0 for Celsius). The default setting is 0.
l
TS2 Temperature Trim: Adjusts temperature sensed by temperature sensor(s) attached to TS2
input. Select -6 to +6for Fahrenheit (-3.0 to +3.0 for Celsius). The default setting is 0.
l
Local Sensor Humidity Trim: Adjusts local sensor humidity percentage. Select -9.0 to+9.0. The
default setting is 0.
l
TS1 Humidity Trim: Adjusts humidity percentage sensed by temperature/humidity sensor
attached to TS1 input. Select -9.0 to +9.0. The default setting is 0.
l
TS2 Humidity Trim: Adjusts humidity percentage sensed by temperature/humidity sensor
attached to TS2 input. Select -9.0 to +9.0. The default setting is 0.

Table of Contents