Max Temperature: Used to prevent the floor from becoming too hot during long heat calls. Select
50 - 110 (Fahrenheit) or 10 - 43 (Celsius). The default setting is 110 for Fahrenheit and 43 for
Celsius.
NOTE: The Max Temperature option is not available when Floor Warming is selected.
l
Lower Setpoint: Limits minimum floor warming setpoint. Select 38 - 100 for Fahrenheit (3 - 38 for
Celsius). Default setting: 38 for Fahrenheit (3 for Celsius).
l
Upper Setpoint: Limits maximum floor warming setpoint. Select 48 - 110 for Fahrenheit (8 - 43 for
Celsius). Default setting: 110 for Fahrenheit (43 for Celsius).
NOTE: The Upper Setpoint must be 10° higher than the Lower Setpoint.
System Type
Select System Type and then configure these settings:
System Type: Select None
NOTE: When System Type is set to None, the following SYSTEM CONTROL settings cannot be
accessed: Fan In Heat, Heat Stages, Cool Stages, Heat Pump Compressor Stages, and Heat Pump
Auxiliary Stages.