Auto Setpoint: Defines how Auto mode operates. Select Dual (default) to use individual heat and
cool setpoints, Single to use one setpoint for both heat and cool, or Disabled to turn off Auto
mode.
l
Setpoint Units: Defines the temperature scale and setpoint incrementation for the thermostat
and sensors. Select 1F (default), 1C, or 0.5C.
l
Temp Display Offset: Adjusts an offset between the space temperature displayed and the
temperature sensed. Select -6 to +6 for Fahrenheit or -3.0 - +3.0 for Celsius. The default setting
is0.
l
Heat Lower Setpoint: Limits the minimum heat setpoint the end user can set. Select 38 - 79
(Fahrenheit) or 3 - 27 (Celsius).The default setting is 38 (Fahrenheit) or 3 (Celsius)
l
Heat Upper Setpoint: Limits the maximum heat setpoint the end user can set. The Upper Setpoint
must be at least 10° (Fahrenheit) or (Celsius) higher than the Lower Setpoint. Select 48 - 89 for
(Fahrenheit) or 8 - 32 (Celsius). The default setting is 89 (Fahrenheit) or 32 (Celsius)
l
Cool Lower Setpoint: Limits the minimum cool setpoint the end user can set. Select 38 - 89
(Fahrenheit) or 3 - 32 (Celsius).The default setting is 59 (Fahrenheit) or 15 (Celsius).
l
Cool Upper Setpoint: Limits the maximum cool setpoint the end user can set. The Upper Setpoint
must be at least 10° (Fahrenheit) or (Celsius) higher than the Lower Setpoint. Select 48 - 99 for
(Fahrenheit) or 8 - 37 (Celsius). The default setting is 99 (Fahrenheit) or 37 (Celsius).
l
Auto Lower Setpoint: Limits the minimum auto setpoint the end user can set. Select 38 - 89
(Fahrenheit) or 3 - 32 (Celsius).The default setting is 59 (Fahrenheit) or 15 (Celsius).
l
Auto Upper Setpoint: Limits the maximum auto setpoint the end user can set. The Upper Setpoint
must be at least 10° (Fahrenheit) or (Celsius) higher than the Lower Setpoint. Select 48 - 99 for
(Fahrenheit) or 8 - 37 (Celsius). The default setting is 99 (Fahrenheit) or 37 (Celsius).
l
Auto Deadband: This sets the separation between the heat and cool setpoints in Auto mode. In
Dual Mode, this is the minimum separation allowed. Select 2.0 (default), 3.0, 4.0, 5.0, or 6.0 for
Fahrenheit or 1.0 (default), 2.0, or 3.0 for Celsius.