EasyManuals Logo

CS Instruments VA 550 User Manual

CS Instruments VA 550
53 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #41 background imageLoading...
Page #41 background image
Operation
VA 550 English V1.21 Page 41 of 53
8.3.3.2 Modbus Settings (2001…2005)
Modbus
Register
Register
Address
No.of
Byte
Data Type
Description
Default
Setting
Read
Write
Unit /Comment
2001
2000
2
UInt16
Modbus ID
1
R/W
Modbus ID 1…247
2002
2001
2
UInt16
Baudrate
4
R/W
0 = 1200
1 = 2400
2 = 4800
3 = 9600
4 = 19200
5 = 38400
2003
2002
2
UInt16
Parity
1
R/W
0 = none
1 = even
2 = odd
2004
2003
2
UInt16
Number of Stopbits
R/W
0 = 1 Stop Bit
1 = 2 Stop Bit
2005
2004
2
UInt16
Word Order
0xABCD
R/W
0xABCD = Big Endian
0xCDAB = Middle Endian
8.3.3.3 Values Register (1001 …1500)
Modbus
Register
Register
Address
No.of
Byte
Data Type
Description
Default
Read
Write
Unit /Comment
1101
1100
4
Float
Flow in m³/h
R
1109
1108
4
Float
Flow in Nm³/h
R
1117
1116
4
Float
Flow in m³/min
R
1125
1124
4
Float
Flow in Nm³/min
R
1133
1132
4
Float
Flow in ltr/h
R
1141
1140
4
Float
Flow in Nltr/h
R
1149
1148
4
Float
Flow in ltr/min
R
1157
1156
4
Float
Flow in Nltr/min
R
1165
1164
4
Float
Flow in ltr/s
R
1173
1172
4
Float
Flow in Nltr/s
R
1181
1180
4
Float
Flow in cfm
R
1189
1188
4
Float
Flow in Ncfm
R
1197
1196
4
Float
Flow in kg/h
R
1205
1204
4
Float
Flow in kg/min
R
1213
1212
4
Float
Flow in kg/s
R
1221
1220
4
Float
Flow in kW
R

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CS Instruments VA 550 and is the answer not in the manual?

CS Instruments VA 550 Specifications

General IconGeneral
BrandCS Instruments
ModelVA 550
CategoryAccessories
LanguageEnglish

Related product manuals