7 — SERIAL COMMUNICATIONS & PROGRAMMING
Curtis 1353 CANopen Expansion Module Manual – June 2017 Return to TOC
pg. 44
CONFIGURATION PROGRAM MENU
PARAMETER ALLOWABLE RANGE DESCRIPTION
Nominal Voltage
1 – 7 Must be set to the vehicle’s nominal battery pack voltage. This parameter is
used in determining the overvoltage and undervoltage protection thresholds
for 1353
1 = 12 V
2 = 24 V
3 = 36 V
4 = 48 V
5 = 60 V
6 = 72 V
7 = 80 V
The Brownout Voltage is determined by the 1353 base type (1353-4xxx
or 1353-6xxx) and cannot be changed. If the B+ voltage stays below the
Brownout voltage for > 64 ms, the 1353 will reset (equivalent to cycling the
KSI). If the B+ voltage rises above the Brownout voltage before 64 ms have
passed, the 1353 will not reset.
Preset Hour 0 – 65535 h Presets hours of the hour meter and resets the minutes to zero.
Restore Type 1, 2 This parameter is used to select the source of the parameters when the 1353
is powered on.
1 = Load parameters from back-up EEPROM block.
2 = Load parameters from normal EEPROM block.
The default value for this parameter is 2. When it is programmed to 1, the
1353 will load all backup parameters after cycling KSI, and then the Restore
Type value will reset to 2.