26
6. Constant tables
Constant
NO
Name Description
Setting
value
Factory
setting
Change
during
operation
Com.
add.
Page
Cd-00
Setting
frequency
Input master speed frequency by keyboard
( frequency command 1)
0.00∼
400.00
10.00
HZ
Yes 128 P42
Cd-01
Selecting
frequency
command
0:Digital input by key board
1:Analog input
2:Analog input (lag)
3:Multi-step function
4:DI UP/DOWN(2)
5:Pulse input
6:Keypad UP/DOWN (1)
7:Keypad UP/DOWN (2)
0󲕏7 0 No 129 P44
Cd-02
Operation
display
1:Output frequency (contain slip boost)
2:Output current
3:Frequency command
1󲕏3 1 Yes 130 P43
Cd-03 Torque mode
0:No auto boost
1:auto boost
0󲕏1 1 No 131 P61
Cd-04
Operation
command
selecting
0:Keyboard operation
1:External terminal (Keyboard stoppable)
2:MODBUS (Keyboard stoppable)
3:External terminal (Keyboard unstoppable)
0󲕏3 0 No 132 P45
Cd-05 Set V/F pattern
1󲕏14: Select from fixed 15 V/F mode.
15: Set by from CD51to CD58 V/F mode.
1󲕏15 2 No 133 P57
Cd-06
Motor rated
current
Set motor rated current as inverter current is 100%.
Set torque boost gain as ratio.
10.0󲕏
100.0
100.0
%
No 134 P62
Cd-07
Torque boost
gain
Please adjust well when folling situation occurred.
1:Increase this value when cable is too long.
2:Decrease this value when motor is vibrating.
0󲕏2.50 0.3 Yes 135 P61
Cd-08
Acceleration
time 1
The time needed for set frequency
from 0 Hz to 50 HZ
0󲕏
6000.0
10.0
sec
No 136 P45
Cd-09
Deceleration
time 1
The time needed for set frequency
from 50 HZ to 0 Hz
0󲕏
6000.0
10.0
sec
No 137 P45
Cd-10
Acceleration
time 2
The time needed for set frequency
from 0 Hz to 50 HZ
0󲕏
6000.0
10.0
sec
No 138 P45
Cd-11
Deceleration
time 2
The time needed for set frequency
from 50 HZ to 0 Hz
0󲕏
6000.0
10.0
sec
No 139 P45
Cd-12
Frequency
command 2
2
nd
step frequency command 0󲕏400.00
20.00
HZ
Yes 140 P53
Cd-13
Frequency
command 3
3
rd
step frequency command 0󲕏400.00
30.00
HZ
Yes 141 P53
Cd-14
Frequency
command 4
4
th
step frequency command 0󲕏400.00
40.00
HZ
Yes 142 P53
Cd-15 Jog frequency Fenquency when jog run 0󲕏60.00
5.00
HZ
Yes 143 P52

Table of Contents