49
Multi-functions analog input
Description: Set filter time by Cd30. Set filter time longer. The ability of reject noise is stronger. But
reactionof input will be corresponsive slower. Please set suitable time by request.
Terminals of IN1 ( 4󲕏20mA), IN2 (0󲕏+10V) and IN3 (0󲕏+10V) are multi-function analog input, the input
specification 10V(20mA) indicates 100%, use Cd31, Cd34 and Cd37 to set enlarge/ reduce magnification,
and Cd33Cd36Cd39 to set bias %. Cd32Cd35Cd38. All functions of multi-function analog input, please
refer to multi-function analog input functions list
.
Notice: Limits of authority level IN3>IN2>IN1
For example: Set Cd32(IN1) and Cd35(IN3)=1 at the same time, and IN1 will not operate when input IN1.
9. Output/ input terminals
Constant
No.
Constant name Settable range Factory setting
Change during
operation
Cd30 Analog input filter time 1󲕏1000 5 O
Cd31 IN1 input gain
0.0 󲕏
1000.0
100.0% O
Cd32 IN1 functions selecting 0󲕏8 0 X
Cd33 IN1 input bias ±100.0 0.0% O
Cd34 IN3 input gain
0.0 󲕏
1000.0
100.0% O
Cd35 IN3 functions selecting 0󲕏8 0 X
Cd36 IN3 input bias ±100.0 0.0% O
Cd37 IN2 input gain
0.0 󲕏
1000.0
100.0% O
Cd38 IN2 functions selecting 0󲕏8 1 X
Cd39 IN2 input bias ±100.0 0.0% O