90
15. Enviroment setting■
DC Bus & current fine tune
Description: This function is to adjust the calibration of voltage positioning on DC BUS between detected
and actual position. The display value is higher when set at bigger figure.
Cd67: 220V series, when setting value 15V equal to 15V。
400V series, can set up to 30V.
Motor specification
Description: CE82󲕏86 : The motor values are shown after execute autotuning.
( CE82󲕏85for FG –Type only)
CE87 : Inverter load specification of inverter (FG –Type only)
1: 150% overload (heavy load model)
2: 120% overload (light load moodel)
Data lock
Information:Data lock to prevent unperfesional operator to input unsuitable data.
Cd98=0 Read only mode: Data lock, but operation frequency could be input by numeric keys or
incresement , decresment keys.
Cd98=1 Simple mode: Some constants could be read and modified.
Cd98=2 Macrocosm mode: All constants could be read and modified.
Constant No. Constant name Settable range Factory setting
Change during
operation
Cd67 DC Bus fine tune ± 30.0V 0.0V X
CE98 Current display fine tune value ± 100.0% 0.0 X
Constant No. Constant name Settable range Factory setting
Change during
operation
CE82 Motor slip 0.00 󲕏 20.00 2.00HZ X
CE83 Motor Noload current 10.0 󲕏 100.0 30.0% X
CE84 Motor pole 2󲕏8 4 pole X
CE85 Motor leakage inductance 0.0󲕏40.0 0% X
CE86 Motor resistance (RS) 0.000 󲕏65.000 By specification X
CE87 Select load 0󲕏1 1 X
Constant No. Constant name Settable range Factory setting
Change during
operation
Cd98 Data lock 0󲕏2 2 X