9
2. Installation and storage
■
◆ FP standard specification
Control method V/F vector PWM control
Frequency accuracy Digital setting:±0.01 Analog setting:±0.5%(35℃)
Frequency resolution Digital setting:0.01HZ Analog setting:(Max. frequency/1024)HZ
Frequency range 0.00 400.00HZ
V/F ratio 14 patterns, or any V/F patterns.
Torque boost Motor autotuning, automatic torque boost (1HZ torque above 150%)
Acce./ Dece. time
0.0 6000.0 sec.(linear, two-step setting)
Brake DC, dynamic brake (below 11KW)
Standard feature
120% overload, jogging speed, upper/lower frequency limit setting, 8-step speed setting, multi-step
function, RS485/RS422 communication, jump frequency, PID control, multi-function DI & analog input
interface
Option card features Analog-digital IO card (under development)
Frequency setting Digital setting by keypad, analog setting by keypad(DC 010V), analog setting(DC 010V, 420mA)
Display
LCD display, 7-segment LED display, frequency, current, voltage, setting value, function, indicators, fault
status
Protection Phase loss, low voltage, over voltage, overload, over current, over heat, subthreshold current
Overload capacity 120% for 1 min, anti-time limit function
Altitude Indoor, altitude 1,000m or lower,
Ambient Temperature -10℃45℃
Vibration Below 0.5 G
Humidity Relative between 45% to 90% (No condensing)
Protection structre Forced air cooling, IP00