EasyManua.ls Logo

CUTES CT-2000FG Series - Page 28

CUTES CT-2000FG Series
103 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28
6. Constant tables
C
onstant
NO
Name Description
Setting
value
Factory
setting
Change
during
operation
Com.
add.
Page
Cd-32
IN1 function
selecting
4󲕏20mA input mode, set IN1 function
0: De-active
1: Analog master speed (1
st
speed, frequency command 1)
2: Adding master speed (analog master speed auxiliary
command)
3: Master speed gain
4:Auxiliary frequency 2
5: Auxiliary frequency 3
6: DC brake current
7:PID feedback value
8:PID command value
0󲕏8 0 No 519 P49
Cd-33 IN1 input bias
Set percentage bias for 4mA when input
±100.0 0.00 Yes 520 P49
Cd-34 IN3 input gain
Set percentage when 10V input
Set percentage 100% when set Cd32 correspond selecting
function 100%
0.0󲕏
100.0%
100.0
%
Yes 521 P49
Cd-35
IN3 function
selecting
0󲕏10V input mode setting, set IN3 function
0: De-active
1: Analog master speed (1
st
step speed,
frequency command 1)
2: Adding master speed (analog master speed auxiliary
command)
3: Master speed gain
4:Auxiliary frequency 2
5: Auxiliary frequency 3
6: DC brake current
7:PID feedback value
8:PID command value
0󲕏8 0 No 519 P49
Cd-36 IN3 input bias
Set percetage bias when 0V input
±100.0 0.00 Yes 520 P49
Cd-37 IN2 input gain
Set percetage bias when 0V input
Set percentage 100% when set Cd32 correspond selecting
function 100%
0.0󲕏
100.0%
100.0
%
Yes 521 P49
Cd-38
IN2 function
selecting
0󲕏10V input mode setting, set IN2 function
0: De-active
1: Analog master speed ( first step speed, frequency
command 1)
2: Adding master speed (Analog master speed auxiliary
command)
3: Master speed gain
4:Auxiliary frequency 2
5: Auxiliary frequency 3
6: DC brake current
7: PID feedback value
8: PID command value
0󲕏8 0 No 519 P49
Cd-39 IN2 input bias Set percetage bias when 0V input ±100.0 0.00 Yes 520 P49
Cd-40
Frequency
command 5
5
th
frequency command 0󲕏400.00
45.00
Hz
Yes 168 P53
Cd-41
Frequency
command 6
6
th
frequency command 0󲕏400.00
50.00
Hz
Yes 169 P53
Cd-42
Frequency
command 7
7
th
frequency command 0󲕏400.00
55.00
Hz
Yes 170 P53
Cd-43
Frequency
command 8
8
th
frequency command 0󲕏400.00
60.00
Hz
Yes 171 P53

Table of Contents