PRS-7910
6 PRS-7910
Dual 1.60 GHz CPUs, 2GB RAM, optional 64 ~150 GB SLC SATA SSD storage memory for
historical data
Capable for data management and communication of the SAS for whole substation or power
plant
CPU usage < 25% during normal service; CPU usage < 50% during massive data treatment
Communication ports:
The 2U 19" chassis supports up to 8 Ethernet ports and 8 serial ports
Non-rotating storage is adopted to avoid vibration
A fully closed chassis with a complete panel
Completely separated spaces for electronic and electrical systems
Designed with anti-interference measures to enhance the device EMC.
W×D×H:425mm×280mm×88.1mm
Standard installation size
2U 19" small space occupation with full feature and flexible configuration
Power supply redundancy
Dual power supply module is an option. The extra power supply module will be placed at the
other side of the device rack and works independently.
Real-time database
The database is compatible with data model IEC 61850 and IEC 103
Support of multiple models including primary/secondary equipment model, association model,
primary schematic diagram model, etc.
Full modeling view and data information
Unified data acquisition and transmission.
History database
Embedded history database
Optional capacity: 64 ~150 GB SLC SATA
Multiple data storage types including historical SOE records, operation reports, wave files,
etc.
Multiple communication protocol support
Standard package for server: IEC 60870-5-101/104, DNP, Modbus
Standard package for client: IEC 60870-5-101/104, IEC 60870-5-103, DNP, Modbus