IEC 61850-3: General requirements
IEC 61850-4: System and project management
IEC 61850-5: Communications and requirements for functions and device models
IEC 61850-6: Configuration description language for communication in electrical substations
related to IEDs
IEC 61850-7-1: Basic communication structure for substation and feeder equipment
Principles and models
IEC 61850-7-2: Basic communication structure for substation and feeder equipment - Abstract
communication service interface (ACSI)
IEC 61850-7-3: Basic communication structure for substation and feeder equipment
Common data classes
IEC 61850-7-4: Basic communication structure for substation and feeder equipment
Compatible logical node classes and data classes
IEC 61850-8-1: Specific Communication Service Mapping (SCSM) Mappings to MMS (ISO
9506-1 and ISO 9506-2) and to ISO/IEC 8802-3
IEC 61850-9-1: Specific Communication Service Mapping (SCSM) Sampled values over
serial unidirectional multidrop point to point link
IEC 61850-9-2: Specific Communication Service Mapping (SCSM) Sampled values over
ISO/IEC 8802-3
IEC 61850-10: Conformance testing
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended
that all those involved with any IEC 61850 implementation obtain this document set.
9.4.2 Communication Profiles
The PRS-7000 series relay supports IEC 61850 server services over TCP/IP communication
protocol stacks. The TCP/IP profile requires the PRS-7000 series to have an IP address to
establish communications. These addresses are located in the menu SettingsDevice
SetupComm Settings”.
1. MMS protocol
IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper
(application) layer for transfer of real-time data. This protocol has been in existence for a number
of years and provides a set of services suitable for the transfer of data within a substation LAN
environment. IEC 61850-7-2 abstract services and objects are mapped to actual MMS protocol
services in IEC61850-8-1.
2. Client/server
This is a connection-oriented type of communication. The connection is initiated by the client, and