PRS-7910
PRS-7910 37
B21
SCSM: IEC 61850-8-1 used
Y
Y
Y
B22
SCSM: IEC 61850-9-1 used
N
N
N
B23
SCSM: IEC 61850-9-2 used
Y
N
Y
B24
SCSM: other
N
N
N
Generic Substation Event Model (GSE)
B31
Publisher side
O
Y
B32
Subscriber side
O
Y
Transmission Of Sampled Value Model (SVC)
B41
Publisher side
O
N
B42
Subscriber side
O
N
Where:
C1: Shall be "M" if support for LOGICAL-DEVICE model has been declared
O: Optional
M: Mandatory
Y: Supported by PRS-7000 series relays
N: Currently not supported by PRS-7000 series relays
9.4.6.2 ACSI Models Conformance Statement
Table 9.4.2 ACSI Models Conformance Statement
Services
Client
Server
PRS-7000 Series
M1
Logical device
C2
C2
Y
M2
Logical node
C3
C3
Y
M3
Data
C4
C4
Y
M4
Data set
C5
C5
Y
M5
Substitution
O
O
Y
M6
Setting group control
O
O
Y
Reporting
M7
Buffered report control
O
O
Y
M7-1
sequence-number
Y
Y
Y
M7-2
report-time-stamp
Y
Y
Y
M7-3
reason-for-inclusion
Y
Y
Y
M7-4
data-set-name
Y
Y
Y
M7-5
data-reference
Y
Y
Y
M7-6
buffer-overflow
Y
Y
N
M7-7
entryID
Y
Y
Y
M7-8
BufTm
N
N
N
M7-9
IntgPd
Y
Y
Y
M7-10
GI
Y
Y
Y
M8
Unbuffered report control
M
M
Y
M8-1
sequence-number
Y
Y
Y