5 Application guidelines
Installer reference guide
10
ERLQ004~008CAV3 + EHBH/X04+08CA
Daikin Altherma - Low Temperature Split
4P313774-1C – 2012.11
Configuration
Setting Value
Unit temperature control:
#: [A.2.1.7]
Code: [C-07]
2 (RT control): Unit operation is
decided based on the ambient
temperature of the user interface.
Number of water temperature
zones:
#: [A.2.1.8]
Code: [7-02]
0 (1 LWT zone): Main
Benefits
Cost effective. You do NOT need an additional external room
thermostat.
Highest comfort and efficiency. The smart room thermostat
functionality can decrease or increase the desired leaving water
temperature based on the actual room temperature (modulation).
This results in:
Stable room temperature matching the desired temperature
(higher comfort)
Less ON/OFF cycles (more quiet, higher comfort and higher
efficiency)
Lowest possible leaving water temperature (higher efficiency)
Easy. You can easily set the desired room temperature via the
user interface:
For your daily needs, you can use preset values and schedules.
To deviate from your daily needs, you can temporarily overrule
the preset values and schedules, use the holiday mode…
Under floor heating or radiators – Wireless room
thermostat
Setup
A Main leaving water temperature zone
B One single room
a Receiver for wireless external room thermostat
b Wireless external room thermostat
The under floor heating or radiators are directly connected to the
indoor unit.
The room temperature is controlled by the wireless external room
thermostat (optional equipment EKRTR1).
Configuration
Setting Value
Unit temperature control:
#: [A.2.1.7]
Code: [C-07]
1 (Ext RT control): Unit operation
is decided by the external
thermostat.
Number of water temperature
zones:
#: [A.2.1.8]
Code: [7-02]
0 (1 LWT zone): Main
Setting Value
External room thermostat for the
main zone:
#: [A.2.2.4]
Code: [C-05]
Configure according to the setup:
1 (Thermo ON/OFF): When
the used external room
thermostat or heat pump
convector can only send a
thermo ON/OFF condition. No
separation between heating or
cooling demand.
2 (C/H request): When the
used external room thermostat
can send a separate heating/
cooling thermo ON/OFF
condition.
Benefits
Wireless. The Daikin external room thermostat is available in a
wireless version.
Efficiency. Although the external room thermostat only sends
ON/OFF signals, it is specifically designed for the heat pump
system.
Comfort. In case of under floor heating, the wireless external
room thermostat prevents condensation on the floor during cooling
operation by measuring the room humidity.
Heat pump convectors
Setup
B
A
a
A Main leaving water temperature zone
B One single room
a Remote controller of the heat pump convectors
The heat pump convectors are directly connected to the indoor
unit.
The desired room temperature is set via the remote controller of
the heat pump convectors.
The space heating/cooling demand signal is sent to one digital
input on the indoor unit (X2M/1 and X2M/4).
The space operation mode is sent to the heat pump convectors by
one digital output on the indoor unit (X2M/33 and X2M/34).
INFORMATION
When using multiple heat pump convectors, make sure
each one receives the infrared signal from the remote
controller of the heat pump convectors.
Configuration
Setting Value
Unit temperature control:
#: [A.2.1.7]
Code: [C-07]
1 (Ext RT control): Unit operation
is decided by the external
thermostat.