5 Application guidelines
Installer reference guide
18
ERLQ004~008CAV3 + EHBH/X04+08CA
Daikin Altherma - Low Temperature Split
4P313774-1C – 2012.11
For more information about connecting the recirculation
connection:
for integrated DHW tank, see "7 Installation" on page 27,
for separate DHW tank, see installation manual of DHW tank.
Configuration
For more information, see "8 Configuration" on page 42.
You can program a schedule to control the DHW pump via the
user interface. For more information, see the user reference
guide.
5.4.7 DHW pump for disinfection
Setup
c
a
b
d f
e g
h
i
a Indoor unit
b DHW tank
c DHW pump
d Heater element
e Nonreturn valve
f Shower
g Cold water
h Domestic hot water OUT
i Recirculation connection
The DHW pump and the installation are field supply and the
responsibility of the installer.
For the integrated DHW tank, the temperature of the DHW tank
can be set to maximum 60°C. If applicable legislation requires
higher temperature for disinfection, you can connect a DHW pump
and heater element as shown above.
If applicable legislation requires disinfection of the water piping
until the tapping point, you can connect a DHW pump and heater
element (if needed) as shown above.
Configuration
The indoor unit can control DHW pump operation. For more
information, see "8 Configuration" on page 42.
5.5 Setting up the energy metering
Via the user interface, you can read out the following energy data:
Produced heat
Consumed energy
You can read out the energy data:
For space heating
For space cooling
For domestic hot water production
You can read out the energy data:
Per month
Per year
INFORMATION
The calculated produced heat and consumed energy are
an estimation, the accuracy cannot be guaranteed.
5.5.1 Produced heat
Applicable for all models.
The produced heat is calculated internally based on:
The leaving and entering water temperature
The flow rate
The power consumption of the booster heater (if applicable) in
the domestic hot water tank
Setup and configuration:
No additional equipment needed.
Only in case a booster heater is present in the system, measure
its capacity (resistance measurement) and set the capacity via
the user interface. Example: If you measure a booster heater
resistance of 17.1 Ω, the capacity of the heater at 230 V is
3100 W.
5.5.2 Consumed energy
You can use the following methods to determine the consumed
energy:
Calculating
Measuring
INFORMATION
You cannot combine calculating the consumed energy
(example: for backup heater) and measuring the
consumed energy (example: for outdoor unit). If you do so,
the energy data will be invalid.
Calculating the consumed energy
Only applicable for EHBH/X04+08 and EHVH/X04+08.
The consumed energy is calculated internally based on:
The actual power input of the outdoor unit
The set capacity of the backup heater and booster heater
The voltage
Setup and configuration: To get accurate energy data, measure
the capacity (resistance measurement) and set the capacity via
the user interface for:
The backup heater (step 1 and step 2)
The booster heater
Measuring the consumed energy
Applicable for all models.
Preferred method because of higher accuracy.
Requires external power meters.
Setup and configuration:
For the specifications of each type of meter, see "15 Technical
data" on page 76.
When using electrical power meters, set the number of
pulses/kWh for each power meter via the user interface.
Consumed energy data for EHVH/X16 and EHBH/X16 models
will only be available if this setting is configured.
INFORMATION
When measuring the electrical power consumption, make
sure ALL power input of the system is covered by the
electrical power meters.
5.5.3 Normal kWh rate power supply
General rule
One power meter that covers the entire system is sufficient.
Setup
Connect the power meter to X5M/7 and X5M/8.