15 Technical data
Installer reference guide
107
ERLQ004~008CAV3 + EHBH/X04+08CA
Daikin Altherma - Low Temperature Split
4P313774-1C – 2012.11
4D079038 page 3
450
400
350
300
250
200
150
Veq 40°C [l]
1,55
1,77
2,19
1,38
1,91
150l
200l
300l
EKHWS*
EHV*
180l
260l
40 42 44
46 48 50 52 54 56 58 60
EHV*S18CA*
EHV*S26CA*
Medium tapping pattern EN16147 (= 2 persons)
Large tapping pattern EN16147 (= 3~4 persons)
Heat loss of domestic hot water tank (4)
Selection guidance of domestic hot water tank volume (3)
Tank temperature (°C)
Heat loss [kWh/24h]
Notes:
(2) Time required to heat up the tank starting from a temp of 10°C up to the indicated temp with the heatpump only.
(3) According to EN16147
(4) According to EN12897
If a higher daily Veq 40°C is required then additional heat up cycles are required within 24 hours. Refer to the operation manual for more information.
Tank
Heat loss [kWh/24h]
Tank
Veq 40°C = amount of water that can be tapped with a temperature of 40°C when the hot water tank is heated till a certain temperature with a cold water inlet temperature of 10°C.
The 40°C is considered as a comfrotable domestic hot water temperature.