Field Setting ESIE09-05
96 Test Operation
(5) Thermostat Control
(5.1) X-control
Thermo off
When the DDC controller maintains level A for more than B minutes, and the thermostat is on,
thermo off is carried out for at least C minutes. After C minutes, thermostat on-conditions are
checked.
Thermo on
When the DDC controller reaches level D or higher (lower for heating) and the thermostat is off
for at least C minutes (refer to thermo off conditions), thermostat on is carried out for at least E
minutes.
Mode n° setting Setting switch n° Setting position n° Setting
51 8 00 level A = 1 (cooling)
01 level A = 1 or 2 (cooling)
6 00 B = 3 min, C = 3 min
01 B = 5 min, C = 3 min
02 B = 7 min, C = 3 min
03 --
04 B = 3 min, C = 5 min
05 B = 5 min, C = 5 min
06 B = 7 min, C = 5 min
07 --
08 B = 3 min, C = 10 min
09 B = 5 min, C = 10 min
10 B = 7 min, C = 10 min
9 00 level A = 5 (heating)
04 level A = 4 or 5 (heating)
Mode n° setting Setting switch n° Setting position n° Setting
51 7 00 D = level 1 (cooling)
02 D = level 2 (cooling)
04 D = level 3 (cooling)
06 D = level 4 (cooling)
08 D = level 5 (cooling)
5 00 E = 3 min
01 E = 5 min
02 E = 10 min
b 00 D = level 1 (heating)
01 D = level 2 (heating)
02 D = level 3 (heating)
03 D = level 4 (heating)
04 D = level 5 (heating)