Field Setting ESIE09-05
98 Test Operation
Heating: Upper & lower limit of T
c
can be chosen
(6.2) Y-control
Since there is no external input to change the T
e
/T
c
value, their values can only be changed by
local setup by means of the Daikin remote controller (during installation).
Cooling: T
e
setting
Heating: T
c
setting
(7) Renewal of Target Refrigerant Temperature (X-control)
When a level of the main pcb is updated, the T
e
/T
c
value of the outdoor is updated
simultaneously, otherwise the T
e
/T
c
value remains constant.
When the DDC level remains constant for A seconds, a level update is executed in the main
pcb.
Mode n° setting Setting switch n° Setting position n° Setting
Lower limit T
c
(°C)
Upper limit T
c
(°C)
51 0 00 30 55
01 35 55
02 40 55
03 43 55
04 30 50
05 35 50
06 40 50
07 43 50
08 30 49
09 35 49
10 40 49
11 43 49
12 30 45
13 35 45
14 40 45
15 43 45
Mode n° setting Setting switch n° Setting position n° Setting
23 (13) 1 01 T
e
= 5°C
02 T
e
= 6°C
03 T
e
= 7°C
04 T
e
= 8°C
05 T
e
= 9°C
06 T
e
= 10°C
07 T
e
= 11°C
08 T
e
= 12°C
201T
c
= 43°C
02 T
c
= 44°C
03 T
c
= 45°C
04 T
c
= 46°C
05 T
c
= 47°C
06 T
c
= 48°C
07 T
c
= 49°C
Mode n° setting Setting switch n° Setting position n° Setting
20 (10) 4 01 A = 60 sec
02 A = 120 sec
03 A = 180 sec
04 A = 240 sec