Field Setting ESIE09-05
106 Test Operation
The numbers in the "No." column represent the number of times to press the SET (BS2) button.
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory set
25 Low noise setting
wxwwx xw
Level 1 (outdoor fan with 6 step or lower)
wxxxxxw
Level 2 (outdoor fan with 5 step or lower)
wxxxxwx
∗
Level 3 (outdoor fan with 4 step or lower)
wxxxwxx
26
Night-time low noise
operation start
setting
wxwwxwx
About 20:00
wxxxxxw
About 22:00 (factory setting)
wxxxxwx
∗
About 24:00
wxxxwxx
27
Night-time low noise
operation end setting
wxwwxww
About 6:00
wxxxxxw
About 7:00
wxxxxwx
About 8:00 (factory setting)
wxxxwxx
∗
28
Power transistor
check mode
w x www x x
OFF
wxxxxxw
∗
ON
wxxxxwx
29
Capacity
precedence setting
w x www x w
OFF
wxxxxxw
∗
ON
wxxxxwx
30 Demand setting 1
w x wwww x
60 % demand
wxxxxxw
70 % demand
wxxxxwx
∗
80 % demand
wxxxwxx
32
Normal demand
setting
wwxxxxx
OFF
wxxxxxw
∗
ON
wxxxxwx