SiBE01-829 Control Specification
Functions and Control 25
3.5 Heating Peak-cut Control
Outline During heating operation, heating peak-cut control is activated according to the temperature of
the indoor heat exchanger to prevent abnormal high pressure.
Detail Conditions for starting
Temperature of the indoor heat exchanger
>
68°C.
While controlling
The compressor halts.
The outdoor fan switches ON/OFF according to the temperature of the indoor heat
exchanger.
Conditions for ending
Temperature of the indoor heat exchanger < 50°C (only for the first time)
or
Reset manually by pressing ON/OFF button (for the second time).
(R8497)
OFF
OFF
ON
ON
50˚C 55˚C 68˚C
Outdoor fan
Compressor