EasyManuals Logo

Daikin FTY35GXV1 User Manual

Daikin FTY35GXV1
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #62 background imageLoading...
Page #62 background image
SiBE01-829 Troubleshooting
Service Diagnosis 51
Troubleshooting
Check No.06
Refer to P.55
Check No.07
Refer to P.56
Check No.09
Refer to P.57
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Open the stop valve.
Check the stop valve.
YES
NO
Is it opened?
(R8506)
Replace the fan motor.
Repair the connector or fan
motor lead wires.
Replace the heat exchanger
thermistor.
Replace PCB.
Correct the connection.
Change the air outlet grille
position.
Clean the heat exchanger.
Change the installation
location.
Check the installation space.
Check the connector connection.
Abnormal
Normal
YES
Normal
Normal
Abnormal
NO
Abnormal
Is it normal?
Judgment
Check No. 09
Check the outdoor fan.
Check No. 07
Check the installation
condition.
Check No. 06
Check the heat exchanger
thermistor.

Table of Contents

Other manuals for Daikin FTY35GXV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTY35GXV1 and is the answer not in the manual?

Daikin FTY35GXV1 Specifications

General IconGeneral
BrandDaikin
ModelFTY35GXV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals